Installation
2-15
2) Check the battery terminal voltage level before connecting it. If the battery voltage is less
than 10V DC, DO NOT use the battery and replace it with a charged battery that measures
at least 10V DC.
3) If the battery passes a visual inspection and the terminal voltage is correct, plug the battery
cable (3089927V10) into the Battery In/Out connector on the power supply module.
4) Fully charge the battery prior to initial use (~10 hours).
Connecting the Radio
A radio which is shipped in the ACE3600 is fully connected. To add a radio to the ACE3600,
use the appropriate radio installation kit. For information on radio types, radio installation kits
and connections, see the Radio Types and Installation Kits chapter.